Trane E18: Control does not see its own send message

Source: Trane manual (PDF) (opens in a new tab) ↗ · Updated

Status codeE18Trane
What does Trane E18 mean?

Control does not see its own send message: the integrated furnace control is not seeing the blower-communication send.

How it shows: 7-segment display on a Trane S9V2 two-stage variable-speed furnace (Service Facts S9V2-SF-2A-EN): E18

Likely causes

  • The control's own blower-communication send path has failed
  • Harness or wiring, if the code changes to E17 when the 4-pin connector is removed

Safe checks for E18

  1. Do not unplug the blower harness with the power on. The chart's test is done with power on, inside a live cabinet
  2. Technicianwith power on, remove the 4-pin motor connector from the IFC. If the code changes to E17, verify the harness and wiring. If it does not change, replace the IFC
Safety firstIf you smell gas, do not touch any electrical switch or use a phone in the building; leave immediately and call your gas supplier from outside. Turn off electrical power at the furnace switch or breaker before opening any panel, and never bypass or jumper a limit, rollout or pressure switch. Gas valve, burner, venting, wiring and control-board work should be done by a licensed HVAC technician.

Capacitors can hold a charge after the power is off. Safety terms.

When to call a pro

Call a licensed HVAC technician. E18 is the control not seeing its own send message. E17 is the control not seeing the motor's reply.

Find a Trane dealer (official locator, opens in a new tab) ↗

Email me this fix

We save your email and this page. Nothing is emailed. We'll only use your email for this request.

Privacy. Deletion requests go to the address on that page.

Request a filter and maintenance reminder

We save your email, this page, and the interval you pick. Nothing is emailed. We'll only use your email for this request.

Privacy. Deletion requests go to the address on that page.

Parts & tools for this fix

Taken from this code's causes or steps. A search link opens Amazon results and does not confirm a fit. Check the model number in the manual.

Furnace blower (circulator) motor: guide

In this code: The control's own blower-communication send path has failed

This one is for a technician to test or replace, so we only explain it and do not link to buy it.

Furnace control board and low-voltage fuse: guide

In this code: Parts list for this code: Integrated furnace control

This one is for a technician to test or replace, so we only explain it and do not link to buy it.