Daikin U4: Signal transmission error between the indoor unit and the outdoor unit

Source: Daikin manual (PDF) (opens in a new tab) ↗ · Updated

Status codeU4Daikin
What does Daikin U4 mean?

Signal transmission error between the indoor unit and the outdoor unit.

How it shows: Service-check code U4 on an ARC466 remote for FTX30NVJU or FTX36NVJU. Hold Timer Cancel for 5 seconds until 00 shows, then press Timer Cancel until a long beep. The operation lamp also blinks for a transmission error.

Daikin U4 on the FTX-N service manual is a signal transmission error between the indoor and outdoor units. It is not A5. A5 is freeze-up protection in cooling or heating peak-cut, and A5 is the code whose checks start with the air path and the indoor filter.

Likely causes

  • Power supply out of specification
  • Wiring error or a broken connecting wire between the indoor and outdoor units (wire No. 3)
  • Defective indoor or outdoor unit PCB
  • Short circuit inside the outdoor fan motor winding

Safe checks for U4

  1. Write the code down, then switch off the outdoor disconnect and the breaker. Leave both cabinets closed
  2. Technicianthe manual checks supply voltage, the interconnecting wires, insulation on terminals 1-3 and 2-3, outdoor LED A, and whether the outdoor fan turns freely
Safety firstIndoor and outdoor mini-split units carry line voltage even when the remote is off. Switch off the outdoor disconnect and the breaker before you touch the unit, and do not open either cabinet. Refrigerant, wiring and control-board work must be done by a licensed HVAC technician.

Capacitors can hold a charge after the power is off. Safety terms.

When to call a pro

U4 is a communication fault, not a filter fault. Do not open the outdoor unit. Call a licensed HVAC technician.

Find a Daikin dealer (official locator, opens in a new tab) ↗

Email me this fix

We save your email and this page. Nothing is emailed. We'll only use your email for this request.

Privacy. Deletion requests go to the address on that page.

Request a filter and maintenance reminder

We save your email, this page, and the interval you pick. Nothing is emailed. We'll only use your email for this request.

Privacy. Deletion requests go to the address on that page.

Parts & tools for this fix

Taken from this code's causes or steps. A search link opens Amazon results and does not confirm a fit. Check the model number in the manual.

Multimeter for appliance and HVAC diagnosis: guide

Technician step in this code: the manual checks supply voltage, the interconnecting wires, insulation on terminals 1-3 and 2-3, outdoor LED A, and whether the outdoor fan turns freely

This one is for a technician to test or replace, so we only explain it and do not link to buy it.