We may earn a commission from links on this page. Learn more about affiliate links

Field guide

Furnace Flame Sensor: Symptoms, Codes and Cleaning

By The Fault Code editorial team · Updated 2026-10-23

Short answer

The flame sensor is a metal rod in the burner flame that tells the control board the gas has lit. If it is coated, the board may not sense flame and will shut the gas off, often a few seconds after ignition. Carrier's manual lists oxide build-up on the flame sensor and says to clean it with fine steel wool; Rheem recommends cleaning it at the start of each heating season by a qualified installer or service agency.

Codes that point to flame sensing

CodeMeaning (from the manual)
Goodman EE6Low flame signal: flame sense microamp signal is minimal
Trane E08Low flame current, but still strong enough to allow operation
Lennox red slow / green fastLow flame signal, below 1.5 microamps
Rheem 12Low flame sense: weak or marginal current, furnace keeps running
Carrier 34Ignition proving failure: flame not sensed
Rheem 13Flame lost after established

What the manuals say

  • Carrier 59SC5: check for oxide build-up on the flame sensor; clean with fine steel wool.
  • Rheem R96V: recommends the flame sensor be cleaned at the start of each heating season with fine steel wool or a Scotch-Brite pad by a qualified installer, service agency or the gas supplier.
  • Trane S9V2 Service Facts: lists a normal flame current range of 0.75 to 3.0 microamps.
  • Rheem FAQ: besides a dirty rod, failed flame sense can come from wrong polarity, a poor equipment ground or incorrect gas pressure.

If the sensor is not the problem

A weak signal after cleaning can mean grounding, polarity or gas pressure issues (see Goodman EEA and Trane E06). These need a technician with a meter.

Safety first: If you smell gas, don’t touch light switches or use a phone inside. Leave the building and call your gas utility from outside. Turn off power to the furnace before opening any panel, and never bypass or jumper a safety switch. Gas, venting, wiring and control-board work is for a licensed HVAC technician.

§FFAQ

Can I clean a flame sensor myself?

Rheem recommends a qualified installer or service agency do it. It involves turning off power and gas and working in the burner area, so if you are not trained, call a technician.

What does a low flame signal code mean?

The board is reading less flame current than it wants. Causes include a coated sensor, poor ground, polarity or gas pressure problems.

§SSources